Click to enlarge image
|
| SF6 Gas Insulated Pad Mount Load Break Switch |
|
 |
■ Underground High Voltage line branching and dividing purpose ■ SF6 gas insulated, Rotating Arc quenching load breaking ■ Single operation tool (3-Position switch) ■ Latch type Spring mechanism
- Convenient extension
- 1 ~ 7 ways in one single tank - Ring Main Unit for over 7 ways
- Natural Interlock system
- Durability
- 10,000 times operation of load break operation - 10,000 times operation of mechanical operation
- Distribution Automation availability
- RTU Built-In type/ Separable type - DNP 3.0, MODBUS, RS232 |
 |
RATINGS |
|
|
Item |
Rating |
Item |
Rating |
|
Rated Voltage(kV) |
15/27 |
Basic Impulse withstand voltage (kV 1.2x50㎲) |
95/125 |
|
Rated Current(A) |
630 |
Control cubicle |
Operation voltage |
AC220V Single phase (Self Power) |
|
Frequency |
50/60 |
Control power |
DC24V |
|
Short time withstand current(kA) |
20/12.5 (R.M.S.) |
Permeable Voltage |
85~110% |
|
Making current Capacity (kA) |
50/32.5 (Peak) |
Power frequency withstand voltage |
2kV 1 minute |
|
Opening and Closing time(sec) |
≤ 0.5sec |
Basic Impulse withstand voltage (kV 1.2x50㎲) |
6kV, 3kA |
|
Power frequency withstand voltage(kV) |
50/60 |
Standard Gas Pressure |
0.5kg / ㎠ G | |
|
|
|
|
| |
|
|
|