Click to enlarge image
|
| SF6 Gas Insulated Pad Mount Switchgear |
|
 |
General |
|
- Optimizing fault area in Underground High Voltage line
- SF6 gas insulation, Vacuum Interruption, Rotating Arc quenching Load breaking
- Magnetic Actuator interrupting mechanism of Breaker
- Latch type Spring charge Mechanism of Load Break Switch
- Single Tank (Dead break type)
|
Characteristics |
|
- Various combination
- 1 ~ 7 ways in one single tank - 1CB ~7CB, 1SW ~ 7SW - Combination available by User's request
- High Reliability
- Maintenance free for Circuit Breaker (10,000 times operation) - Maintenance free for Load Break Switch (5,000 times of operation)
- Self power
- Complete protection cooperation
- ANSI. IEC. ESB and User designed curve - RTU Built-In OCR |
 |
RATINGS |
|
|
Item |
Rating |
Item |
Rating |
|
Rated Voltage(kV) |
15/27 |
Basic Impulse withstand voltage (kV 1.2x50㎲) |
95/125 |
|
Rated Current(A) |
630 |
Control cubicle |
Operation voltage |
AC 1Ф 220V |
|
Frequency |
50/60 |
Control power |
DC24V |
|
Short circuit interrupting current(kA) |
20/12.5 (R.M.S.) |
Permeable Voltage |
85~110% |
|
Making current Capacity (kA) |
50/32.5 (Peak) |
Power frequency withstand voltage |
2kV 1 minute |
|
Interrupting time(Cycle) |
≤ 3 |
Basic Impulse withstand voltage (kV 1.2x50㎲) |
6kV, 3kA |
|
Power frequency withstand voltage(kV) |
50/60 |
Standard Gas Pressure |
0.7kg / ㎠ G | |
|
|
|
|
| |
|
|
|